Siting of appliance
Greenstar Heatslave II External appliances are suitable for
external installation only. Appliances should be installed
at a suitable location onto a fixed, permanent and rigid
surface. There must be sufficient hard-standing around
the appliance to allow for servicing. Appliances must be
installed on a flat, level surface to ensure that condensation
does not enter the primary heat exchanger. Appliances
should not be installed where there is a potential for
excessive ground water coverage. Tarmac and wood
hard-standings are not recommended.
Flue system
For all external boilers, consideration should be given to
the location of the appliance and its flue outlet in relation
to windows, doors and air vents. Greenstar Heatslave II
appliances can be connected to the Greenstar Oilfit plume
management system.
Site preparations and guidance
(External models)
950mm
640mm
770mm
Casing dimensions
Top view, left flue Top view, right flue
600mm
2,500mm
600mm
BASE
FRONT
600mm min.
Side view, rear flue Top view, rear flue
Installation and service clearances
The minimum clearances shown below should be allowed
for installation and servicing. It is strongly recommended
that the flue terminal faces away from walls to reduce the
possibility of “wetting” occurring. Care should be taken to
ensure that pipework leaving the appliance and entering
the building should not be exposed. The appliance should
be sited as close to the dwelling as possible.
50mm
10mm
2,500mm
FRONT
Plan
view
FRONT
10mm
50mm
Plan
view
FRONT
2,500mm
45mm85mm
600mm
Plan
view