For full technical information on pipe size, insulation
and different condensate pipework methods, please
see Installation, Commissioning and Servicing
Instruction Manual.
Important points to consider when siting a condensate
drainage pipe:
Where a new or replacement boiler is being installed,
access to an internal “gravity discharge” point should
be one of the factors considered in determining
boiler location
The condensate pipe must be a minimum of 22mm dia.
plastic pipe
The condensate pipework must fall at least 52mm per
metre towards the outlet and should take the shortest
practicable route
Ensure there are no blockages in the pipe run.
Internal connections
In order to minimise risk of freezing during prolonged cold
spells, the following methods of installing a condensate
drainage pipe should be adopted, in order of priority.
Wherever possible, the condensate drainage pipe should be
routed and terminated so that the condensate drains away
from the boiler under gravity to a suitable internal foul water
discharge point such as an internal soil and vent stack.
A suitable permanent connection to the foul waste pipe
should be used. (see fi g. 1)
Condensate pipework
Condensate
discharge
from boiler
Universal
connector
Soil and
vent stack
22mm dia.
Min. 450mm
and up to
three storeys
Fig. 1 Disposal to soil vent stack (internal and external models).
For external models increase pipe size and insulate pipework.
Alternatively if the fi rst option is not possible, an internal
kitchen or bathroom waste pipe, washing machine waste
pipe, etc. can be used. (see fi g. 2)
22mm dia.
Condensate
discharge
from boiler
Universal
connector
Visible air break
at plug hole
Sink or basin with
integrated overflow
75mm sink
waste trap
75mm
min.
Fig. 2 Disposal to a waste pipe (internal models)
Condensate
discharge
from boiler
Universal
connector
22mm dia.
Visible air break
at plug hole
Sink or
basin with
integrated
overflow
75mm sink
waste trap
75mm
min.
Condensate
pump
Fig. 3 Condensate pump disposal (internal models)
Condensate pump
Where “gravity discharge” to an internal termination is not
physically possible, or where very long internal runs would
be required to reach a suitable discharge point, condensate
should be removed using a proprietary condensate pump,
of a specifi cation recommended by the boiler or condensate
pump manufacturer.
The pump outlet pipe should discharge to a suitable
internal foul water discharge point such as an internal soil
and vent stack, internal kitchen or bathroom waste pipe,
washing machine waste pipe, etc. A suitable permanent
connection to the foul waste pipe should be used.
(see fi g. 3 and 4)
Universal
connector
22mm dia.
Condensate
discharge
from boiler
Pipework
transition
Insulate &
increase pipe
size to 32mm
25mm min.
Condensate
pump
Fig. 4 Condensate pump to external disposal (internal models)