4. Control circuits
4.6. Control circuits for a controlled braking of the
drives for an E-stop or power failure
For those drives coupled as an electronic drive via the NC control, and which
cannot accept a phase-angle error with a power failure or an E-stop.
The DC bus voltage is not short-circuited. This means that power is available
for a controlled braking of the drives.
The energy stored or regenerated in the DC bus must be greater than the
energy required to energize asynchrous drives or to execute a return action.
For an E-stop or if a KDV monitor is tripped, drives are stopped by the NC
control unit under drive regulation.
The NC bridge (X10/13 - X10/14) must be closed!
The mains contactor must not be permitted to switch off the drive
enable signal of the drives !
The mains contactor is immediately switched off when the E-stop is tripped.
There is a controlled braking of the drives by the NC control unit.
When the NCB contacts are jumpered, the signal for command-to-
zero will be suppressed if there is a power fault. The superordinate
control must assure that the drive is stopped. This high priority
control must monitor the UD contact of the KDV 2.3 and bring the
drive to a halt whenever the contact should open.
There will otherwise be an uncontrolled coasting of the drives if the
power supply is faulty!