Typical installations
Open (conventional) fl ued appliances must not be installed
in a bedroom, bathroom or bed-sitting room.
Before installation commences it must be checked that:
The chimney is structurally sound and free of obstructions
The chimney has been thoroughly swept to remove
deposits since it was last used.
The fl exible fl ue pipe is only suitable for lining chimneys
that conform to the Building Regulations and it should not
be used as a chimney on its own or outside a masonry or
ueblock chimney.
All the fl exible liner and adaptors must be within the
chimney with rigid stainless steel fl ue pipe connecting to
the boiler.
The fi rst 600mm of the stainless steel fl ue pipe off the
boiler must be vertical with no bends or restrictions.
There must be at least a 25mm clearance between the
stainless steel fl ue pipe and any combustible material.
The data label must be secured onto the chimney or
chimney hearth using the plate provided.
If it is not possible to attach the plate to the chimney,
the plate can be attached, in a visible position, next to
the electricity consumer unit.
Do not attach the data plate or label to the fl ue system.
The terminal should not be modifi ed and an extra cowl or
cover must not be fi tted. The boiler is designed so that
any rain that enters the fl ue will be directed down to the
condensate drain.
Calculating the length:
L maximum = boiler maximum minus 1m*.
(Each 45º bend has a 0.5m equivalent fl ue length)
*If the chimney has an additional offset, then L will be reduced by an extra metre.
**The top 45º bend may not be required if there is sufficient room in the chimney
to turn the flexible liner through 45º within the chimney. The stainless steel
section must be adequately supported.
L max
A
B
C
E
G
F
D
**
A Boiler
B Stainless steel vertical section
(min. 600mm)
C Maximum 2 bends at 45°
D Fire stop plate/inspection plate
E Centralising spacer
F Flexible liner
G Chimney cowl