4.5 FLUE INSTALLATION
HORIZONTAL FLUE (60/100mm diameter)
For vertical flues and 80/125mm horizontal flues, please
refer to separate instructions supplied with the flue kit.
Basic instructions for the 60/100mm diameter flue are
shown below.
Fig. 37 Flue turret centre
4.5.1 MEASURING THE FLUE (STANDARD FLUE):
B Measure from the outside of the wall to the centre line
of the flue turret to determine length L.
B Subtract 50mm from the length L to give the correct
dimension to the flue elbow connection.
B If the length L falls within the telescopic range of 350
to 570mm or 570 to 790mm using the longer
telescopic flue, then no cutting will be required.
B If the required length is less than 350mm the standard
telescopic flue can be modified, refer to fig. 39.
B If the required length is greater than 570mm, then the
longer telescopic flue, giving a range of 570 - 790mm,
can be used
B If the required length is greater than 790mm, then flue
extensions will have to be used. Refer to the 60/100
Horizontal Flue Instruction manual provided in the
telescopic flue kit.
B Refer to section 3.8 for flue options.
Adjusting the telescopic flue length:
Fig. 38 Standard telescopic flue
Extend tube (1) by withdrawing from tube (2) to achieve
the flue length required, between 350 - 570mm.
Secure with screw provided and seal joint with the
aluminium tape supplied.
4.5.2 REDUCING THE TELESCOPIC FLUE LENGTH:
The flue terminal MUST be fitted with the 'TOP' label
uppermost to allow the correct fit and use of the plume
management system.
Fig. 39 Reducing the standard terminal
B Remove securing screws (3) to detach the terminal
assembly from the turret.
B Slide terminal section (2) from the terminal assembly
and discard.
B To use terminal (1) without cutting remove the
location lug (4) on the inner flue tube (5) and remove
any burrs.
To reduce the flue length further:
Fig. 40 Further reduction
B Mark the length required for the terminal as shown
(min. 130mm) and cut square, taking care not to
damage the tubes.
B Remove any burrs and chamfer the outer edge of the
tubes to assist ease of connection and prevent seal
damage.
To ease assembly of flue components, apply
silicone lubricant to sealing surfaces.
200 mm
189 mm
Edge
of
case
WALL
6720643895-29.1Wo
6720643895-30.1Wo
570 mm
350 mm
L
2
1
Ensure that the “TOP” label is facing up
before securing the flue section to the
turret.
The aluminium tape is not required when
reducing the terminal.
6720643895-31.1Wo
2
3
1
4
5
6
1
130 mm
265 mm
MIN
6720643895-32.2Wo