Bosch GREENSTAR HEATSLAVE II EXTERNAL 12/18 Service Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
35
2m
1m
52mm
104mm
2,500
Drainpipe
External
oil boiler
750
or
w
indow
300
300
600
12
13
14
9
10
11
7. Minimum 600mm straight fl ue before any bend on a
conventional fl ue.
8. 750mm between a vertical structure and a fl ue terminal.
9. 1,000mm below a Velux or dormer window, 300mm
above or to either side of the Velux or dormer window
or any opening on a sloping roof.
10. 600mm above the highest point of an intersection with
a roof.
11. Any fl ue must fall back towards the boiler by 3° or
52mm for every metre of fl ue so that the condensate
drains back to the boiler for disposal.
12. 300mm to any vertical sanitary pipework or drain pipe.
13. Flue clearance must be at least 300mm above ground
or balcony level. Terminal guards must be fi tted if the
ue is less than 2 metres from the ground or if a person
could come into contact with the fl ue terminal.
14. 2,500mm between terminals facing each other.