9-11
Comms > Dialler Reporting >
Swinger Dialler
MENU 5-4-5
(*** System Wide Parameter ***)
0 6
Swinger Dialler can be used to prevent a faulty or run-a-way
PIR from continually re-triggering the zone and reporting to
the base station.
The Swinger Dialler count sets the maximum number of times
an individual zone can trigger an alarm during the current
arming cycle before it is locked out.
If this option is not programmed, the panel will continue to
report the alarm signal until the system or area is disarmed.
Only zones that have been programmed for Lockout Dialler in
MENU 3-1-7 — Report Options will follow the Swinger Dialler
count.
Press [MENU] + [5] + [4] + [5]. The keypad will display the
current Swinger Dialler count.
Swinger Dialler
6
Press 0-9 OK to SAVE
Using the numeric keys, enter the new Swinger Dialler count
then press [OK] to save and exit or press [MENU] to exit
without saving. Valid entries are 0 - 15 / 0 = disabled
Comms > Dialler Reporting >
Burg Report Delay
MENU 5-4-6
0 0 0
(*** System Wide Parameter ***)
SECONDS
This menu programs how long the panel will delay reporting
Burglary alarm reports. Only burglary (non-re) zones that
have been programmed for Delay Report in MENU 3-1-7 —
Report Option will follow the Burglary Report Delay time.
Press [MENU] + [5] + [4] + [6]. The keypad will display the
current burglary report delay time.
Burg Report Delay
000 seconds
Press 0-9 OK to SAVE
Using the numeric keys, enter the new report delay time then
press [OK] to save and exit or press [MENU] to exit without
saving. Valid entires are 0 to 255 seconds.
1)
2)
1)
2)
Comms > Dialler Reporting >
Fire Report Delay
MENU 5-4-7
0 0 0
(*** System Wide Parameter ***)
SECONDS
This menu programs how long the panel will delay reporting
re zone alarm reports. Only re zones that have been
programmed for Delay Report in MENU 3-1-7 — Report Option
will follow the Fire Report Delay time.
Press [MENU] + [5] + [4] + [7]. The keypad will display the
current Fire Report Delay time.
Fire Report Delay
000 seconds
Press 0-9 OK to SAVE
Using the numeric keys, enter the new report delay time then
press [OK] to save and exit or press [MENU] to exit without
saving. Valid entires are 0 to 255 seconds.
Comms Registration
Comms > Registration >
Customer
MENU 5-5-0
Reserved for future use.
Comms > Registration >
Installer
MENU 5-5-1
Reserved for future use.
Comms Testing
Comms > Comms Test >
Send Test Report
-
-
MENU 5-9-0
This menu allows you to test the reporting functions of the
Solution control panel by manually sending a Test report to
the receiving party (i.e. security company monitoring station,
mobile telephone etc).
Enter [MENU] + [5] + [9] + [0]. The keypad will prompt that it is
in the process of sending a test report.
Comms Testing in
progress. Please wait.
To Go Back Press OK
If the test is successful, the keypad will prompt:
1)
2)
1)
2)