Report/Log Entry/Exit Installer Menu
Setting this option will cause the panel to make a log entry and to
send a report to the base station when the installer enters and exits
Installer programming mode. The entry/exit reports will follow the
System Route.
Report/Log Program Data Changed
Setting this option will cause the panel to make a log entry and to
send a report to the base station when the installer has changed
programming data. The data changed reports will follow the System
Route.
Arm Only Installer PIN
Setting this option will prevent the installer PIN holder from disarming
the system. Normally the installer PIN is able to arm and disarm the
system.
Auto Exit Installer Menu In 5 Minutes
Setting this option will cause the panel to automatically terminate
Installer programming mode after 5 minutes of no activity on the
keypad. If this option is not set, the panel will remain in Installer
programming mode until manually terminated.
Auto Exit Service Mode In 2 Hours
Setting this option will cause the panel to automatically terminate
service mode after 2 hours of no activity on the keypad keys. If this
option is not set, the panel will remain in the service mode until it is
manually terminated.
Factory Defaulting Allowed
Setting this option will allow the panel to be defaulted back to the
factory setting using the the on board push button switch. See below
for defaulting instructions.
If this option is not set then manual defaulting will not function and
the only way to default the panel will be by using the current installer
PIN. If the installer PIN is not know then the panel will need to be
returned to Bosch for defaulting. A $50.00 charge applies for this
service.
i
Note
Defaulting the panel does not erase all events in the history
event log.
System >Options >
Language
MENU 7-7-5
0 = English 0
1 = Alternate Language
This menu allows you to select the language that will be
displayed on the keypad. You have a choice between English
(default) or a second language (determined by the country
that the control panel is shipped to).
Enter [MENU] + [7] + [7] + [5]. The keypad will display the
following:
Language
0
Press 0-9 OK to SAVE
1)
Using the numeric keys, enter the language option as required
then press [OK] to save and exit or press [MENU] to exit
without saving.
System Testing
System > System Testing >
Walk Test All Zones
-
-
MENU 7-9-0
This menu allows you to test all zones within an area at the
same time.
Press [MENU] + [7] + [9] + [0]. The keypad will display a list of
areas that are available to walk test zones.
Using the up and down arrow keys, select the area that you
want to walk test, then press [OK]. Alternatively, you can enter
the area number, then press [OK]. The keypad will begin to
scroll all zones that need to be tested.
To test Z001 open/close
Zone 1
Press OK or MENU
Open and close each zone that needs to be tested. A zone that
has been successfully tested will no longer scroll on the keypad
display. When all zones have been tested, the keypad will
display.
Selected zones have been
Tested OK
Press OK or MENU
Press [OK] to save and exit or press [MENU] to exit without
saving.
System > System Testing >
Battery Test
-
-
MENU 7-9-1
This menu allows you to test the panels standby battery. The
battery test will last about two minutes and the keypad will
display the voltage of the battery during the test.
Press [MENU] + [7] + [9] + [1]. The keypad will display the
battery voltage whilst under test:
Battery test in progress.
Please wait..
Voltage = 13.4V
To Go Back Press OK
If the battery has passed the test, the keypad will display:
Battery Test Passed
Tested OK
Press OK or MENU
2)
1)
2)
3)
4)
1)
2)