D9112B | Program Entry Guide | EN | 83
Bosch Security Systems | 2/04 | 74-06145-000-D
9.1 Area Wide Relays
Each area can be assigned a unique relay number
for each of the events listed in this section. Do not
use the same relay for different functions, or share
the same relay between areas, unless they are
appropriate for sharing as indicated in the Program
Record Sheet.
Area
Default: 1
Selection: 1 to 8
Enter the area number you are programming.
A# Alarm Bell
Default: A
Selection: Blank, 1 to 128, A, B, or C
This relay activates when a non-fire point assigned to
the specified area causes an alarm bell response.
Burg Time
and
Burg Pat
must be programmed in
Bell Parameters. This relay activates according to the
bell pattern and remains active until the bell time
expires.
The following point index entry combinations cause
the Alarm Bell relay to respond when the point goes
into alarm:
Silent Bell: No
Audible After 2 Failures: Yes (if the report
does not get through to the receiver after two
attempts.)
Fire Point: No
A# Fire Bell
Default: A
Selection: Blank, 1 to 128, A, B, or C
This relay activates when a fire point assigned to the
specified area causes a fire alarm response.
Fire
Time
and
Fire Pat
must be programmed in “Bell
Parameters.” This relay activates according to the
bell pattern and remains active until the bell time
expires.
0101
0101
0101
The default program uses the same relay
that is assigned for Burglary Bell output in
all areas. If both a Fire Alarm and a Burglary
Alarm are activated at the same time, the
Fire Alarm has priority. When assigning fire
points to the area, it is recommended that
you program the Fire Bell output for a
different relay. For example, program the
Fire Bell output for relay B and install a
D136 relay in the panel.
The following point index entry combinations cause
this relay to respond when the point goes into alarm:
Silent Bell: No
Fire Point: Yes
A# Reset Sensors
Default: C
Selection: Blank, 1 to 128, A, B, or C
Activates for five sec. when the Reset Sensors
function is entered at a command center assigned to
the area specified. It also activates for the amount of
time programmed in Area Parameters
Verify Time
when an alarm verification point assigned to the area
goes into alarm (also see Point Index for an
explanation of alarm verification points).
If you use a common relay for several areas,
program the command center scope to include the
same common areas and make sure the user
authority level for those areas includes the ability to
Reset Sensors. Failure to do so can cause troubles in
areas where the user has no control.
When relay C is activated. It interrupts the positive
12 VDC at terminal 8 on the D9112 circuit board.
To use relay C, install a D136 relay in the panel.
A# Late To Close
Default: Blank
Selection: Blank, 1 to 128, A, B, or C
Activates when the closing window expires for the
specified area. It remains activated until midnight, or
until another closing window starts, or the panel is
reset, whichever occurs first.