Testing Your System
Zone Test
The Zone Test is used to confirm that detectors will report alarms to the keypad. A Zone Test works on all zones, except 24-hour zones and
fire zones. While the keypad is in a Zone Test, no control panel alarms will activate an alarm, except 24-hour zone alarms and fire alarms;
these will override the Zone Test function.
This test requires you to manually alarm each zone.
At the start of the test, if so programmed, a report is sent to the central station followed by reports on the individual zones as they are tested.
Upon completion of the zone test, a test restoral report is sent to the central station.
If this test is performed from a Master keypad, it must be in Single Partition Mode. System Tests are not available from RF (wireless) keypads.
Note: It is recommended that the system be tested weekly.
* DS7447/DS7447E only
** DS7445/DS7445i only
Type of Test
Command
Sequence
What Will Happen What To Do
Zone Test [PIN] + [#] [8] [1]
“Test Zone” will display followed by the zone number
of any zones that have not been tested.*
The zone LEDs of any untested zones will flash.**
“Now Testing” will display followed by the zone
number of the zone that is currently being tested.*
The zone LED for the zone currently being tested
will turn on steady. **
As each zone is tested, the display turns to “Test
Zone” and indicates the remaining untested zones.*
As each zone is tested, its LED turns off.**
Test each zone a
s
instructed by you
r
installing company.
Exit the Zone Tes
t
using [PIN] + [#]