Solution-144
Installation Manual Programming Overview
4-4
Bosch Security Systems 10/12 BLCC600BI
ZONE ARRAY
The feature allows you to view the condition of all zones
on the panel in banks of 16 zones at a time. From the
installer programing mode press MENU 3-0-1 to access
the zone array.
Use the [] and [] arrow keys to scroll up and down the
zone banks and press [OK] or [MENU] when finished.
The following information can be displayed depending
on the current zone status.
N= NORMAL
S = SHORTED
A= ALARM
T= TAMPER
- = DISABLED
0000000001111111
1234567890123456
NSA-ANAT--------
Press
 OK or MENU
In the above example screen,
N = Zone 01 and 06 are Normal (Sealed)
S = Zone 02 is Shorted
A = Zone 03,05,07 are in Alarm (Unsealed)
T = Zone 08 is in Tamper Alarm (Unsealed)
- = Zone 04, 09-16 are Disabled (Unused)
OUTPUT ARRAY
This feature allows you to view output status in groups of
16. From the installer programing mode press MENU 4-0-
2 to access the output array.
Use the [] and [] arrow keys to scroll up and down the
output banks and press [OK] or [MENU] when finished.
The following information can be displayed depending
on the current zone status.
N = NORMAL - Off Condition
T = TRIGGERED - On Condition
F = FAULT - Overload Condition
- = DISABLED
1) Enter [MENU] + [4] + [0] + [2] and use the up and
down arrows to select the output group to view.
2) Use the up and down arrows at any time to move to
a new group. The keypad will display the following
output array information for outputs 1 to 16.
0000000001111111
1234567890123456
NNNNN---TF------
Press  OK or MENU
In the above example screen,
N = Outputs 01 to 05 are Normal (Off )
F = Output 10 has a Fault (Overload)
T = Output 09 is Triggered (On)
- = Outputs 05 to 08 and Outputs 11 to 16 are
Disabled or Not Available
DOOR ARRAY
This feature allows you to view door status in groups of 16.
From the installer programing mode press MENU 4-0-4 to
access the output array.
Press [OK] or [MENU] when finished.
The following information can be displayed depending
on the current zone status.
L = Door Locked
U = Door Unlocked
O = Override
- = Disabled or Not Available
0000000001111111
1234567890123456
LLLLL---UUUUO---
Press  OK or MENU
In the above example screen,
L = Doors 01 to 05 are Locked
O = Door 13 has a Override condition
U = Doors 09 to 12 area Unlocked
- = Doors 06 to 08 and Doors 14 to 16 are Disabled or
Not Available
TESTING THE SYSTEM
You will need to be in programming mode before
accessing the test functions listed below.
Walk Test
Use the walk test command MENU 3-9-0 to test and verify
that all zones work correctly.
External Audible Test
Use MENU 4-9-0 to test and verify that all horn speakers
operate. This test will sound the horn speaker for two
seconds.
Internal Audible Test
Use MENU 4-9-1 to test and verify that all 12 VDC sirens
operate. This test will sound the siren for two seconds.
Strobe Test
Use MENU 4-9-2 to test and verify that the strobe operates.
This test will turn on the strobe until you manually stop
the test.
Battery Test
Use MENU 7-9-1 to test the back-up battery that is
connected to the control panel.
Communication Test
Use MENU 5-9-0 to test the telephone reporting capability
of the control panel. You can also activate a communication
test by holding down the Test / Mail key on the keypad.