Bosch 6000 Installation Manual Page 63

  • Download
  • Add to my manuals
  • Print
  • Page
    / 170
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 62
Solution-144
Installation Manual Area Programming
6-9
Bosch Security Systems 10/12 BLCC600BI
Exit Time A1
060 Seconds
Press 0-9 OK to SAVE
3) Using the numeric keys, enter the required entry
time in seconds. Valid times are 1 - 255 seconds, 0
= No Exit Time.
4) Press [OK] to save and exit or press [MENU] to exit
without saving.
Areas > Timers >
Entry Time 1
-
MENU 2-8-1
0 2 0
Seconds
This menu allows the installer to set the entry delay time
for each area. The entry delay time can be programmed
between 0 and 255 seconds. This should be set to allow
the user enough time to turn the area off (disarm) before
an alarm condition occurs (eg. end of entry time = alarm).
The entry delay timer starts as soon as a user faults a zone
programmed as burglary delay 1 (eg. opens the front
door) after the area has been turned on and the exit delay
timer has expired.
1) Press [MENU] + [2] + [8] + [1]. The keypad will
display a list of areas.
A1 Security System
A2 Area 2 Name
A3 Area 3 Name
Press  OK or MENU
2) Highlight the area required to change, then press
[OK] to select. The keypad will display the current
entry time set for the area selected.
Entry Time 1 A1
020 Seconds
Press 0-9 OK to SAVE
3) Using the numeric keys, enter the required entry
time in seconds. Valid times are 1 - 255 seconds, 0
= No exit time.
4) Press [OK] to save and exit or press [MENU] to exit
without saving.
Areas > Timers >
Entry Time 2
-
MENU 2-8-2
0 4 0
Seconds
This menu allows the installer to set the entry delay time
for each area. The entry delay time can be programmed
between 0 and 255 seconds. This should be set to allow
the user enough time to turn the area off (disarm) before
an alarm condition occurs (eg. end of entry time = alarm).
The entry delay timer starts as soon as a user faults a zone
programmed as burglary delay 2 (eg. opens the back
door) after the area has been turned on and the exit delay
timer has expired.
1) Press [MENU] + [2] + [8] + [2]. The keypad will
display a list of areas.
A1 Security System
A2 Area 2 Name
A3 Area 3 Name
Press  OK or MENU
2) Highlight the area required to change, then press
[OK] to select. The keypad will display the current
entry time set for the area selected.
Entry Time 2 A1
040 Seconds
Press 0-9 OK to SAVE
3) Using the numeric keys, enter the required entry
time in seconds. Valid times are 1 - 255 seconds, 0
= No entry tTime.
4) Press [OK] to save and exit or press [MENU] to exit
without saving.
Areas > Timers >
Part Entry Time
-
MENU 2-8-3
0 6 0
Seconds
This menu sets the time period which a keypad will sound
its warning tone after a zone is triggered in Part On or Part
2 On modes. The user must disarm the area before the
Part Entry Time expires, otherwise an alarm condition will
be triggered.
At factory default, when an area has been turned Part On
or Part 2 On and exit time has finished, violating a non 24hr
burglary zone will start the part entry time. The keypad
will sound the hi/lo tone for a period of 60 seconds before
the control panel sound an alarm or until the user turns
the area off.
Page view 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 169 170

Comments to this Manuals

No comments