Solution-144
Installation Manual Input Programming
7-4
Bosch Security Systems 10/12 BLCC600BI
ZONE PROPERTIES
Inputs > Zone Properties >
Zone Name
-
MENU 3-1-0
Z o n e 1 N a m e
This menu allows you to program the name for each zone.
Zone names can be up to 20 characters long.
1) Enter [MENU] + [3] + [1] + [0] and use the up and
down arrows to highlight the Zone in the list then
press [OK]. Alternatively, you can enter the zone
number directly and press [OK].
2) User the arrow and number keys to move and
change text. When the Zone Name is complete,
press [OK]. At any time you can press the [OFF] key
to clear the text from the current cursor position to
the end of the line.
Zone Name Zn1
Zone 1 Name
Press  OK to SAVE
See Alpha Text Programming in Section 4 -
Programming Overview for further detail on entering
alpha text.
Inputs > Commands >
Smoke Sensor Reset
-
-
MENU 3-0-5
This command allows you to reset smoke sensors.
When initiated this command will cause any outputs
programmed as Event Type 49 — Smoke Sensor GND in
the chosen area to turn off for 10 seconds.
1) Enter [MENU] + [3] + [0] + [5] and use the up and
down arrows to highlight the area that you want to
reset the smoke detectors in then press [OK].
Smoke Detector reset in
progress. Please wait
2) The keypad will automatically return to the menu
when all smoke detectors in the area has been
reset.
Smoke detectors must have the negative power
terminal connected to an output programmed as
Event Type 49 for this command to work.
ZONE DEFAULT TABLE
The table below lists the default values for all zone parameters in the control panel. Zones marked as Not Used do not
require EOL resistors to be fitted.
Programming Zone 1 Zone 2 Zone 3 Zone 4 Zones 5 - 16 Zones 17 - 144
Zone Name Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 to 16 Zone 17 to 144
Zone Type 1 = Delay 1 5 = Handover 5 = Handover 5 = Handover 3 = Instant 0 = Not Used
Area Assignment 1 1 1 1 1 1
Pulse Count 0 0 0 0 0 0
Pulse Count Time 120 120 120 120 120 120
Door Assignment 0 0 0 0 0 0
Report Route 2 2 2 2 2 2
Reporting Options
Lockout Dialler Y Y Y Y Y Y
Report Alarm Y Y Y Y Y Y
Report Troubles Y Y Y Y Y Y
Report Bypass Y Y Y Y Y Y
Reserved N N N N N N
Reserved N N N N N N
Report Restores Y Y Y Y Y Y
Delay Reporting N N N N N N
Zone Options
Lockout Siren Y Y Y Y Y Y
Silent Alarm N N N N N N
Inverted Seal N N N N N
N
Bypass Allowed Y Y Y Y Y Y
Sensor Watch N N N N N N
Armed In Part On Y Y Y Y Y Y
No EOL Required N N N N N N
Test On Exit N Y Y Y Y Y
Table 21: Zone Defaults