• DOK-DIAX01-MAIN+2AD+1M-ANW1-EN-E1,44 • 07.97
3. Controller Functions
Para-Analo
g
M
Parameter protocol !
Parameter
P16
P19
A06
Designation
PQ-FUNCT
LOAD LIM
FUNCT2
Function
M output indicates load in per cent
+10V = 100%
M output indicates voltage +10V as relates to value
in LOAD LIM, (kW or %) as specified in A06
torque or power output threshold, depends on A06
Parameter LOAD LIM is output-related, value in kW
Parameter LOAD LIM is torque-related, value in %
M output indicates torque,
+10V = 10 * (number in LOAD LIM) * Nm
Value range or value
< 0 >
< 16 >
0....99
< 0 >
< 1 >
< 512 >
S R Q
S R Q
( % or kW )
Note:
Analogue output M is designed to monitor static drive utilization. The
voltage that it delivers is smoothed to suppress high-frequency variations
in drive utilization. This produces a clearer display.
When the torque value is output at analogue output M, the percent drive
utilization that is otherwise output at this point appears at analogue N.
If parameter LOAD LIMIT (PQRS 19) is used as a torque threshold,
power threshold or as a weighting factor for torque output, then the LOAD
LIMIT signal output is also active for this value.
Figure 63: Parameter for analogue output M