Bosch Solution 64 Specifications Page 44

  • Download
  • Add to my manuals
  • Print
  • Page
    / 108
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 43
Solution 64
|
Installer Guide
|
Input Programming
7-4
Bosch Security Systems | 11/05 | BLCC110I
Inputs > Commands >
Smoke Sensor Reset
-
-
MENU 3-0-5
This command allows you to reset smoke sensors. When
initiated this command will cause any outputs programmed as
Event Type 49 — Smoke Sensor GND in the chosen area to turn
o for 10 seconds.
Enter [MENU] + [3] + [0] + [5] and use the up and down arrows
to highlight the area that you want to reset the smoke
detectors in then press [OK].
Smoke detector reset in
Progress. Please wait
The keypad will automatically return to the menu when all
smoke detectors in the area has been reset.
i
Note
Smoke detectors must have the negative power terminal
connected to an output programmed as Event Type 49 for this
command to work.
Zone Properties
Inputs > Zone Properties >
Zone Name
-
MENU 3-1-0
Z o n e 1 N a m e
This menu allows you to program the name for each zone.
Zone names can be up to 16 characters long.
Enter [MENU] + [3] + [1] + [0] and use the up and down arrows
to highlight the Zone in the list then press [OK]. Alternatively,
you can enter the zone number directly and press [OK].
User the arrow and number keys to move and change text.
When the Zone Name is complete, press [OK]. At any time you
can press the [OFF] key to clear the text from the current cursor
position to the end of the line.
Zone Name Zn001
Zone 1 Name
Press  OK to SAVE
i
Note
See Alpha Text Programming in Section 4 - Programming
Overview for further detail on entering alpha text.
1)
2)
1)
2)
Inputs > Zone Properties >
Zone Type
MENU 3-1-1
1
This menu allows you to congure the zone type or behaviour
for every zone in the system. Each zone should be assigned
to a Zone Type that denes the way in which the panel will
respond when an alarm is triggered on that zone. Refer to
the table and descriptions below for the available Zone Type
selections.
Zone Types
0 = Zone Not Used
1 = Burglary Delay 1 (Entry Timer 1)
2 = Burglary Delay 2 (Entry Timer 2)
3 = Burglary Instant 1 (With Exit Delay)
4 = Burglary Instant 2 (No Exit Delay)
5 = Burglary Handover
6 = Burglary 24-Hour
7 = Tamper 24-Hour
8 = Hold Up 24-Hour (Silent & Invisible)
9 = Medical 24-Hour
10 = Panic 24-Hour
11 = Fire 24-Hour
12 = Reserved
13 = Keyswitch Zone
14 = Display Only
15 = 24-Hour Non Burglary
Table 17: Zone Types
Press [MENU] + [3] + [1] + [1] and use the up and down arrows
to highlight the Zone in the list then press [OK]. Alternatively,
you can enter the zone number directly and press [OK].
Use the up and down arrow keys to select the Zone Type
required then Press [OK] to save and exit or press [MENU] to
exit without saving.
Zone Type Zn001
01 - Burglary Delay 1
Press  0-9 OK to SAVE
0 Zone Not Used
Program the zone type as zero if the zone is not being used.
1 Burglary Delay 1
Zones programmed as Delay 1 will cause Entry Timer 1 to start when
tripped. The user must disarm the area before entry timer expires
or an alarm will occur. Zones set as Burglary Delay 1 are only active
when the area is armed. See MENU 7-2-1 — Entry Time 1 to set the
required delay time.
2 Burglary Delay 2
Zones programmed as Delay 2 will cause Entry Timer 2 to start when
tripped. The user must disarm the area before entry timer expires
or an alarm will occur. Zones set as Burglary Delay 2 are only active
when the area is armed. See MENU 7-2-2 — Entry Time 2 to set the
required delay time.