Solution 64
|
Installer Guide
|
Output Programming
8-4
Bosch Security Systems | 11/05 | BLCC110I
30 - Chime Zone Faulted
This event type will cause the output to operate when a specic
Chime Zone is triggered and reset when the Chime Zone reseals.
If the event assignment for this output is set to zero (all areas), then
the output will operate as soon as any chime zone is triggered
provided that Chime Mode is on in those areas. The output will reset
when all Chime Zones are resealed. For this event type to work Chime
Mode must be turned on. See MENU 2-0-5 — Chime On/O
31 Auto Arm Pre-Alert
This event type will cause the output to operate when the Auto Arm
Pre-Alert Timer is active and reset when the Pre-Alert Timer expires or
a valid user code is entered.
32 Ready To Arm All On
This event type will cause the output to operate when the area is
disarmed and all zones in the area are sealled. The output will reset
when the area is armed or when a zone becomes unsealled.
If the event assignment for this output is set to zero (all areas), then
the output will only operate if all areas are disarmed and all zones
are sealled. The output will reset if any area is armed or if any zone
becomes unsealled.
33 Ready To Arm Part On
This event type will cause the output to operate when the area is
disarmed and all zones in the area which are to be monitored in Part
On mode are sealled. The output will reset when the area is armed or
when a Part On zone becomes unsealled.
If the event assignment for this output is set to zero (all areas), then
the output will only operate if all areas are disarmed and all Part On
zones are sealled. The output will reset if any area is armed or if any
Part On zone becomes unsealled.
34 Ready To Arm Part 2 On
This event type will cause the output to operate when the area is
disarmed and all zones in the area which are to be monitored in Part 2
On mode are sealled. The output will reset when the area is armed or
when a Part 2 On zone becomes unsealled.
If the event assignment for this output is set to zero (all areas), then
the output will only operate if all areas are disarmed and all Part 2 On
zones are sealled. The output will reset if any area is armed or if any
Part 2 On zone becomes unsealled.
35 Close’ Report Sent OK
This event type will cause the output to operate when the Closing
report has been acknowledged (Kissed-O) by the control room
receiver. The output will reset when the area is disarmed. If the
output has been assigned to multiple areas then it will only reset
when all areas have been disarmed.
36 External Siren (Spk Beeps)
This event type will cause the output to operate when any audible
alarm occurs. The output will reset when the system or area is
disarmed.
This event type will also generate speaker beeps when the system or
area is armed via a RF Keyfob, the Programmable Input Terminal or
Keyswitch zone.
1 beep when the area is disarmed
2 beeps when the area is armed All On
3 beeps when the area is armed Part On
37 Internal Siren
This event type will cause the output to operate when any audible
alarm occurs. The output will reset when the system or area is
disarmed. No speaker beeps are generated for this event type.
38 Alarm Any (Silent or Audible)
This event type will cause the output to operate when any silent or
audible alarm occurs. The output will reset when the system or area is
disarmed
39 Fire Alarm
This event type will cause the output to operate when any audible re
zone or keypad emergency re alarm occurs. The output will reset
when the system or area is disarmed.
40 Burglary Alarm
This event type will cause the output to operate when any audible
burglary alarm (including keypad emergency panic, medical and
tamper alarm) occurs. The output will reset when the system or area
is disarmed.
41 Silent Alarm
This event type will cause the output to operate when any silent alarm
occurs (including silent re and silent keypad emergency alarms). The
output will reset when the system or area is disarmed.
42 Duress Alarm
This event type will cause the output to operate when a user initiates
a Duress alarm.
43 Keypad Medical
This event type will cause the output to operate when a silent or
audible medical alarm has been initiated from the keypad. The
output will reset when the system or area is disarmed.
To initiate a medical emergency via the keypad, simultaneously press
and hold the [7] and [9] keys for 2 seconds.
44 Keypad Fire
This event type will cause the output to operate when a silent or
audible re alarm has been initiated from the keypad. The output will
reset when the system or area is disarmed.
To initiate a re emergency via the keypad, simultaneously press and
and hold the [4] and [6] keys for 2 seconds.
45 Keypad Panic
This event type will cause the output to operate when a silent or
audible panic alarm has been initiated from the keypad. The output
will reset when the system or area is disarmed.
To initiate a panic emergency via the keypad, simultaneously press
and hold [1] and [3] keys.
46 Keypad Tamper
This event type will cause the output to operate when the tamper
circuit on the rear of the keypad is triggered. The output will reset
when a valid user PIN is entered.
47 Access Denied
This event type will trigger if you attempt to enter an incorrect code
more times than programmed in the pin retry count location. The
event assignment will be the area number for this event type.