D9112B | Program Entry Guide | 9.0 Relay Parameters EN | 82
Bosch Security Systems | 2/04 | 74-06145-000-D
9.0 Relay Parameters
Relays provide basic alarm system functions (such as
Bell Output and Reset Sensors) as well as a number
of more advanced functions typically used in
association with system annunciation devices.
Up to three on-board voltage-output relays can be
installed on the D9112 circuit board. (see the D9112
Operation and Installation Manual for instructions).
The D9112 can also control up to 128 dry contact
form “C” relays when optional D8129 OctoRelay
Modules are installed.
One relay is provided with the D9112 to provide a
+12 VDC Alarm Bell output from the D9112
terminal 6 (Relay A).
Two additional optional relay sockets are provided
with the D9112. The D9112 provides a +12 VDC
Alternate Alarm output from terminal 7 (Relay B),
and a +12 VDC Switched Aux Power output from
terminal 8 (Relay C). Optional relay sockets require
Bosch Security Systems D136 Relays.
If relay activity is reported to the receiver (see Phone
Routing), on-board relays are reported as follows: A
= 253, B = 254, C = 255.
Up to sixteen D8129 OctoRelay Modules can be
connected to the D9112 to provide 128 dry contact
form “C” relays. You can set DIP switches on each
D8129 to use a group of eight numbered relays as
shown in the D9112 Operation and Installation Manual.
0101
0101
0101
Check relay status after reprogramming or
resetting the panel. All relays are turned off
after the panel is reset. Certain relay
functions are checked by the panel each
minute and resume the correct state after
the reset. Other relays must be manually set
to the correct state (using Cmd 54).
Table 32: Relay Status
Resumes Proper State
within 1 min.
Functions must be
manually reset with
Command 54
Alarm Bell Late to Close
Perimeter Fault Command 9
Summary Fire Force Armed
Summary Trouble Duress
Printer 18 Fail Command 7
Communications Fail Log % Full
Silent Alarm
Fire Bell
AC Fail
Summary Alarm
Keypad Fail
Printer 19 Fail
Area Armed
Watch Mode
Area Fault
Battery Trouble
Summary Fire Tbl
Printer 17 Fail
Phone Fail
Relay Follows Point
Reset Sensors