Bosch D9112B Installation Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
D9112B | Program Entry Guide | 1.0 Panel Wide Parameter EN | 13
Bosch Security Systems | 2/04 | 74-06145-000-D
Table 3: Phone Routing
Report Group Description
Blank
Not reported to this phone number.
P Primary: Send all reports from this group to this phone number. Only one primary phone
allowed per group.
B Backup: Send reports from this group to this phone if the report is not received by the primary
phone number. A primary phone route must also be programmed for this Report Group in order
to dial the backup phone number. Only one backup phone allowed per group.
D Duplicate: Send all reports from this group to this phone number after they are sent to the
other phone (primary or backup). A primary phone route must be programmed in order to send
a duplicate report. Only one duplicate phone allowed per group. Failure to send a duplicate
report does not generate any user notification or central station report.
Press the [SPACE] bar to scroll through the
selections. Press [ENT] when the correct selection
appears in the display.
0101
0101
0101
If the D5200 buzzes when you make an
entry, you made a routing error. If you enter
the same route on two different phones for
a particular Report Group the D5200
buzzes. When it buzzes, it accepts the entry
currently in the display, and changes the
matching routing entry to blank. This
disables routing the Report Group to the
other phone.
Recheck the phone routing for the Report
Group for each phone if the programmer
buzzes.
Table 4: Phone Routing Worksheet – Fire
Alarm/Res (Fire Alarm/Restoral)
Report Type Phone 1 Phone 2 Phone 3 Phone 4
Fire Alarm
x x
Fire Restoral (after alarm)
x x
Table 5: Phone Routing Worksheet – Fire Tbl/Res (Fire Trouble/Restoral)
Report Type Phone 1 Phone 2 Phone 3 Phone 4
Fire Trouble
x x
Fire Walk Start
x x
Missing Fire
x x
Fire Restoral (after Trouble or Missing)
x x
Fire Walk End
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16 17 18 ... 95 96

Comments to this Manuals

No comments