D9112B | Program Entry Guide | 7.0 Point Index EN | 73
Bosch Security Systems | 2/04 | 74-06145-000-D
P## Entry Delay
Default: See
Program Record Sheet
Selection: 5 sec. to 600 sec.
This program item does not require an entry unless
the point
Type
and
Point Response
entry provides
entry delay on this point. The panel ignores this
entry if the point
Type
does not provide entry delay.
When a Perimeter or Interior point is programmed
for entry delay, entry delay time is always provided
when that point is tripped before an instant point.
Points programmed for “instant” alarms generate
alarms immediately, even during entry or exit delay.
If a delay point trips while the area is in entry delay,
the panel compares the remaining entry delay time
to the time programmed for the newly tripped point.
If the newly tripped point’s entry delay time is less
than the remaining time, it shortens the entry delay
time.
Enter the time allowed prior to this delay point
going into alarm. Make entries in five sec.
increments. The programmer does not allow off-
increment entries.
P## Entry Tone Off
Enable/disable the entry delay warning tone for this
point.
This panel ignores this entry point if the
Type
does
not provide entry delay.
Default: See
Program Record Sheet
Selection: Yes or No
Yes Disable entry delay tone. You may
want to disable the entry tone in high
security applications where you do
not want to annunciate entry delay.
Caution:
The possibility of false alarms
increases if the entry delay warning is
not used.
No A tone sounds at command centers
when this point initiates entry delay.
P## Silent Bell
Default: No
Selection: Yes or No
Yes
Activate the
Silent Alarm
relay when
this point goes into alarm. Command
centers do not sound the alarm tone
for non-fire points.
No
Activate either the
Fire Bell
or
Alarm Bell
relay and sound the
alarm tone at command centers when
this point goes into alarm. If this is a
Fire Point it activates the
Fire Bell
replay programmed in Relay
Parameters, otherwise, it activates the
Alarm Bell
relay. The amount of
time and pattern of the relay
activation is programmed by area in
Bell Parameters.
P## Ring Until Restored
Default: See
Program Record Sheet
Selection: Yes or No
Yes The relay programmed to provide fire
alarm output for this point cannot be
de-activated until the point restores to
normal. If the point restores and the
fire alarm is not silenced from the
command center, the fire alarm
output continues until
Fire Bell
time
expires. If the point does NOT
restore, the fire alarm output
continues even after bell time expires.
Use this option for fire applications to
meet the requirement that audible
alarms cannot be silenced until the
fault condition clears. The area cannot
be armed until the bell is silenced.
No The relay programmed to provide fire
alarm output for this point can be de-
activated before the point restores to
normal.