Bosch D9112B Installation Manual Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 96
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
D9112B | Program Entry Guide | 3.0 User Interface EN | 54
Bosch Security Systems | 2/04 | 74-06145-000-D
View Pt Status
Default: E
Selection: Blank, E, or P
View Point Status: View points assigned to the area
where the command center is assigned. This function
shows point text and the electrical condition
(normal, open, short) of each point in the area.
0101
0101
0101
Points 72 and 136 appear in the Point Status
List. Notice that text for Commands 7 and 9
is followed by a MISSING condition on point
72 and point 136. Points 72 and 136 serve
dual purposes. They are used for Command
7 and Command 9, and they are also used to
supervise the data expansion bus. When you
see that points 72 and 136 are missing, do
not be alarmed. When these points are
missing the point bus is normal.
See Command Center Function Selections in the
introduction to the Command Center Functions
programming module for descriptions of selections.
L## View Pt Stat
Default: See
Program Record Sheet
Selection: Blank or E
View Point Status: See Authority Level Selections in
the introduction to the Authority Lvl Assign
programming module for descriptions of selections.
Walk Test
Default: E
Selection: Blank, E, or P
Walk Test [COMMAND] [4] [4]:
Test controlled points in disarmed areas within the
Scope
of the command center without sending
reports to the central station.
See Command Center Function Selections in the
introduction to the Command Center Functions
programming module for descriptions of selections.
L## Walk Test
Default: See
Program Record Sheet
Selection: Blank or E
Walk Test: See Authority Level Selections in the
introduction to the Authority Lvl Assign programming
module for descriptions of selections.
Fire Test
Default: P
Selection: Blank, E, or P
Fire Test [COMMAND] [5] [8]:
Test 24-Hour points in areas within the
Scope
of the
command center where the function is entered.
When a Fire Test is initiated one person can
typically test a fire system without assistance. The
following features are provided with the Fire Test
Mode:
Central station report is transmitted when the
Fire Test Mode is initiated and when it is
terminated.
Local alarm annunciation without report
transmission.
All reports from 24-Hour points within the
Scope of the command center are
suppressed during Fire Test.
Automatic smoke detector reset (executing Reset
Sensors from the Function Menu is not required
after each device is tested).
Command centers equipped with an alpha-
numeric display show a sequential count after
each point is activated and restored.
Printed record of each alarm test response is
available if a local printer is installed and has the
Scope
required to record events from the area
being tested (D9131 Printer Interface required).
See Command Center Function Selections in the
introduction to the Command Center Functions
programming module for descriptions of selections.
L## Fire Test
Default: See
Program Record Sheet
Selection: Blank or E
Fire Test: See Authority Level Selections in the
introduction to the Authority Lvl Assign programming
module for descriptions of selections.
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 95 96

Comments to this Manuals

No comments