106 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
Local alarm annunciation and event printing; no reports are sent to the central station
receiver.
Automatic smoke detectors reset for all Fire points programmed with P## Resettable as
Yes.
D1255 Keypad displays a sequential count and the text for the point after each point is
activated and restored.
If enabled in Routing, Walk Start and Walk End Reports are sent to the central station
receiver at the beginning and end of the test.
L## Send Report
Send a Test Report from any keypad assigned to an area where the user has authority.
Access Control Functions
The following five functions are used to control the doors from the keypad. These features are
not available with the D7212GV4.
Use the following functions to control the doors from the keypad. Users can have authority to
access the Door Control and can use all or part of the functions within.
L## Door Control
This item only allows programming access to the following three sub-prompts. It does not
affect the user’s access to Cycle Door, Unlock Door, and Secure Door.
The following prompts are sub-functions of Door Control.
NOTICE!
A# Verify Time for Fire points that is programmed with Yes for P## Alarm Verify is ignored
during the Fire Walk Test.
Default: Authority Levels 1, 15: Enabled (E)Authority Levels 2-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
13 Send Report [COMMAND][4][1] or [COMMAND][4][2]
NOTICE!
All doors display when this function is selected. This function does not follow the scope of the
keypad.
Default: Authority Levels 1-2, 15: Enabled (E)Authority Levels 3-14: Blank (-)
Selection: - or E
Function No. Function Name Alternate Keystroke
14 Door Control [COMMAND][4][6]
This feature is not available with the D7212GV4. Keep the default setting.
NOTICE!
Cycle Door, Unlock Door, and Secure Door cannot be accessed through the Function List.
Door Control must be added to the Function List to access the door control functions, or
COMMAND 46 can be used.
NOTICE!
Cycle Door must be enabled for all three sub-functions to operate. If Cycle Door is disabled,
all three sub-functions do not operate.