D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 123
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
When it reaches 100% capacity (memory logger is full and previously stored events will be
overwritten), the control panel generates a local LOG OVERFLOW event. The control panel
does not call RPS again until it downloads the log and the Log % Full percentage is again
reached. These events are also sent to the control panel's event log and to the local printer(s)
if installed.
Summary Fire
Enter the number of the relay that activates when any Fire point in the system (P## Type 0,
P## Fire Yes) enters into alarm. This relay provides a steady output until all Fire points in the
system return to normal. Refer to Section Fire Summary Sustain, page 175 for details on
alternate operation.
Summary Alarm
Enter the number of the relay that activates when a Non-fire point enters into alarm. This relay
provides a steady output until the alarm is acknowledged by a valid passcode, then cleared
from alarm memory with an acknowledgment at the keypad.
Summary Fire Trouble
Activates when any Fire point in the control panel is in trouble, or if a Fire Supervision point is
missing. This relay provides a steady output until all Fire points restore to a normal condition.
Summary Supervisory Fire
Activates when any Fire Supervisory point in the control panel is in a supervisory condition
(off-normal). This relay provides a steady output until all Fire Supervisory points are restored
to a normal condition.
Summary Trouble
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
NOTICE!
This relay does not activate for silent and invisible alarms.
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4
Default: 0
Selection: 0, 1 to 128 A, B, or C for D9412GV4
0, 1 to 64, A, B, C for D7412GV4
0, 1 to 24, A, B, or C for D7212GV4