D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 25
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
3. Program a Phone 1 for RG1 Backup Destination
4. Enable all applicable events to be included in Route Group 1.
- Phone (Refer to Section 3.1 Phone, page 17.)
1. Select Phone 1.
2. Program Phone 1 with the applicable central station receiver phone number.
- Enhanced Communication (Refer to Section 3.4 Programming Path Numbers and Network
Addresses for Enhanced Communications, page 40).
1. Set Enhanced Comm to Yes.
2. Program Path 1 Nework Address with the applicable central station network address.
3. Program Path 1 Port Num with the applicable central station network receiver port
number.
4. Enter a non-zero value for the Path 1 Poll Rate.
3.3.5 Programming a Duplicate Report
Select Yes for each available route number to allow an event within a group to send a report
to multiple groups. For instance, if fire alarms are programmed for Route Group 1 and Route
Group 2, a fire alarm sends a report first to Route Group 1, followed by a duplicate report to
Route Group 2.
3.3.6 Routing Destination Communication Failures
When the R# Primary Device fails to connect to the central station receiver after two
attempts by phone, the R# Backup Device phone number will be dialed. The central station
will receive the original event with a COMM TROUBLE PHONE # = (1, 2, 3, or 4) message
added. This event does not occur if there is no backup phone number. If the R# Primary
Device is an SDI Path, the central station receives the original event with a COMM TROUBLE
RG8 SDI## event modifier. Refer to Table 3.4, Page 25.
Table 3.4 SDI Path Number by Device
When all attempts to both the R# Primary Device and R# Backup Device fail, a COMM FAIL
RG# event is generated. COMM RESTORE RG# events are generated when a successful
report (via phone or network) or a successful poll (via network) is sent over either route
within the failed Route Group, even if the report is sent using a different Route Group.
The same COMM TROUBLE conditions occur if the control panel does not receive a positive
acknowledgement to a poll from the central station receiver after the configured number of
retries. Refer to Section Path # Poll Rate, page 41.
3.3.7 Message Prioritization within a Route Number
The GV4 Series Control Panels meet the digital reporting requirements for UL 864. Fire Alarm
Events have the highest priority and reports are sent first for each group. Other events are
sent in the following order: Panic, Duress, Medical, Intrusion Alarm, Supervisory, and all
troubles and restorals.
DevicePath 1Path 2Path 3Path 4
SDI 88 88 89 90 91
SDI 92 92 93 94 95
SDI2-1 11 21 31 41
SDI2-2 12 22 32 42
NOTICE!
To comply with NFPA and UL 864 (D9412GV4 and D7412GV4), program Route 1 to send a
report of only Fire Alarm Events to ensure the fastest reporting time.