D9412GV4/D7412GV4/D7212GV4 AUXPARM | en 177
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Passcode Length
During entry delay, the code is accepted when the last digit is pressed to disarm the area.
For SIA CP-01 Compliance:
Passcode Length must be set to 3, 4, 5, or 6.
Swinger Count
When a point has P# Swinger Bypass set to Yes, the value set in Swinger Count determines
the number of times the point is faulted erroneously within an hour before it is automatically
bypassed.
For SIA CP-01 Compliance:
P## Swinger Bypass can be Yes or No. If P## Swinger Bypass is Yes, Swinger Count must be
1 or 2.
Remote Warning
Upon remote arming, the output pulses on for 2 sec. Upon remote disarming, the output
pulses on, off, on, off for 2 sec each.
For SIA CP-01 Compliance:
NOTICE!
To meet UL requirements, the combined Entry Delay time and Abort Window time must not
exceed 60 sec. For Entry Delay time programming information, refer to Section P## Entry
Delay, page 134.
UL note: Maximum settings for residential use:
Exit Delay =120 sec
Entry Delay = 45 sec bell
Off-Premise Transmission = 60 sec
Maximum settings for commercial use:
Exit Delay = 120 sec no line security
Entry Delay = 60 sec bell
Off-Premise Transmission = 60 sec
The system must use both the bell and off-premise transmission.
Default 0
Selection: 0, 3, 4, 5, or 6
0 Disabled; sets a variable length for user passcodes, allowing for
backward compatibility
3, 4, 5, or 6 Sets a fixed length to all user passcodes.
Default 2
Selection: 1, 2, 3, or 4
1, 2 Number of fault or trouble bypasses allowed per hour for SIA CP-01
compliance.
3 Optional fault count
4 Value used for backward compatibility with previous control panel
operation.
Default No
Selection: Yes or No
Yes The system uses the Alarm Bell output to annunciate the arming and
disarming of an area through remote software, or a remote arming
device such as a key switch or keyfob.
No No remote warning occurs to annunciate the arming and disarming of
an area through remote software, or a remote arming device such as a
key switch or keyfob.