Bosch D9412GV4 Installation Guide Page 165

  • Download
  • Add to my manuals
  • Print
  • Page
    / 210
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 164
D9412GV4/D7412GV4/D7212GV4 Schedules (Skeds) | en 165
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Sked Number
S## TimeEdit
Select whether the user can edit the time of this sked from the keypad.
S## Function Code
RPS automatically retrieves the appropriate sub-menu when the user enters a function code.
Refer to the following examples:
Example 1: When Function Code 1 (Arm Area) is entered, the S## Area 1 [through #]
prompt appears.
Example 2: When Function Code 3 (Bypass a Point) is entered, the S## Point Number
prompt appears.
After you program the parameter choices associated with the Sked function, program the
sked for date, day of week, time, or holiday.
Default: Yes
Selection: Yes or No
Yes The user can edit the time of this sked from the keypad and determines
if this sked appears in the CHG SKED display.
No The user cannot edit the time of this sked from the keypad and the sked
does not appear in the CHG SKED display.
Default: 0
Selection: 0 = Not In Use, 1 to 24, 28, 29
1 Arm Area: This function simulates the Master
Arm Delay keypad function. Entries in the S##
Area # prompts define the area(s) this sked
arms. The sked can arm multiple areas. If any
point is faulted when the sked executes, it is
force armed regardless of the A# Force Arm
Bypass Max setting.
S## Area 1[through #]
Default: No
Selections: Yes or No
Enable the sked to arm the
areas indicated with Yes.
Yes
No
Arm Area #.
Do not arm Area #.
2 Disarm Area: This function emulates the
DISARM #? or DISARM ALL? keypad function
list options. Entries in the S## Area # prompts
define the area(s) this sked disarms. The sked
can disarm multiple areas.
S## Area 1[through #]
Default: No
Selection: Yes or No
Enable the sked to disarm
the areas indicated with
Yes.
Yes
No
Disarm Area #.
Do not disarm
Area #.
3 Bypass a Point: This function emulates the
Bypass Pt? keypad function. The entry in the
S## Point Number prompt defines the point
this sked bypasses. The point can be
bypassed only if Bypassable is programmed
Yes in the point index assigned to the point.
The bypass is reported if the Bypass Reports
is enabled by the point index settings
assigned to the point. The sked can bypass
one point.
S## Point Number
Default: Blank
Selections: Blank, 1 to 127,
129 to 247 for D9412GV4,
1 to 75 for D7412GV4, 1 to
40 for D7212GV4
Enter the number of the
point the sked bypasses.
Blank (0)
1 to 127,
129 to 247
No point is
bypassed
Point to bypass
Page view 164