148 en | Points D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
P### Debounce
The debounce count is the number of times the control panel scans a point before generating
an alarm. Scan cycles are 300 ms.
For appropriate settings consult the manufacturer’s instructions for the device connected to
this point.
P### Relay Codes/Relays
Use this option to activate a relay when the point is faulted. Refer to Table 5.2.
Default: 2
Selection: 1 to 15
1 .300 sec
2 .600 sec
3 .900 sec
4 1.2 sec
5 1.5 sec
6 1.8 sec
7 2.1 sec
8 2.4 sec
9 2.7 sec
10 3.0 sec
11 3.3 sec
12 3.6 sec
13 3.9 sec
14 4.2 sec
15 4.5 sec
NOTICE!
Use an entry of two or higher. Interior Follower points need a Debounce value of at least
three.
NOTICE!
Door points assigned to D9210C modules need a Debounce value of at least four (D9412GV4
and D7412GV4).
NOTICE!
P### debounce does not apply to wireless points.
Default: Points 1..8 are set to Relay Codes 1..8 respectively
All other points are 0.
Selection: 0: Disabled
1 to 8
NOTICE!
Relays do not activate for Fire Supervisory or Non-Fire Supervisory points.