D9412GV4/D7412GV4/D7212GV4 ACCESS CONTROL (D9412GV4/D7412GV4) | en 199
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
D# Shunt Time
Enter the amount of time that the Door point is shunted to allow a user to open the door. The
duration of time should be sufficient so that the opened door does not cause the point to
enter into a trouble, alarm, or faulted condition.
D# Buzz Time
Enter the amount of time the buzzer output sounds to notify the user that the strike was
activated and the door is ready to open. The buzzer stops as soon as the door is opened.
D# Extend Time
Enter the amount of time that strike, buzz, and shunt activation is prolonged if a door is left
open and the shunt time expires. At the end of the programmed extend time, the buzzer
continues to buzz until the door closes. If programmed, the point assigned to the door
indicates a trouble, alarm, or fault at the keypad.
D# Deactivate On Open?
Determines if the strike deactivates immediately upon physically opening the door.
Default: 10 sec
Selection: 0 to 240 sec
0 Shunt Time is not programmed for this door.
1 to 240 The shunt activates for the amount of time programmed.
Default: 2 sec
Selection: 0 to 240 sec
0 Buzz Time is not programmed for this door.
1 to 240 The buzzer sounds for the amount of time programmed.
NOTICE!
A separate buzzer is required. Many readers have an internal buzzer that is not affected by
Buzz Time.
Default: 10 sec
Selection: 0 to 30 sec
NOTICE!
The CLOSE DOOR # display on keypad does not activate if D# Extend Time is set to 0.
NOTICE!
Regardless of how the Door point is programmed, the system generates a Trouble Door Left
Open Event while the system is disarmed, and an Alarm Door Left Open Event if the system is
armed and the door is held open beyond Extend Time. Door Closed - Restoral Events are
generated after the door is held open past Extend Time and the door returns to normal.
Default: Yes
Selection: Yes or No
Yes Strike deactivates when the door is opened after a valid Access Granted
request.
No Strike remains activated for the amount of the programmed strike time
whether door is opened or closed.
NOTICE!
In order for this function to work, a point needs to be assigned to the door.