Bosch D9412GV4 Installation Guide Page 54

  • Download
  • Add to my manuals
  • Print
  • Page
    / 210
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 53
54 en | Panel and Area Wide Parameters D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
P## Auto Functions Event
P## RPS Event
P## Relay Event
P## Point Event
P## User Chng Evt
3.8 RPS Parameters
Use these program items to enable remote programming software (RPS) functions in the
control panel using the on-board phone connection or a Network Interface Module. Refer to
Section 3.5 SDI RPS/Enhanced Communications Configuration, page 45 for more information on
these types of remote programming.
3.8.1 Uploading and Downloading Reports
If the control panel is programmed to send reports in ModemIIIa
2
reporting format, when RPS
contacts the control panel and the passcode is incorrect, the control panel sends an RPS
Access Fail Report to the central station receiver. RPS Access Fail might indicate a wrong RPS
passcode when communicating with the control panel, or a valid RPS session was abnormally
terminated.
RPS ACCESS OK is sent according to phone routing when a Disconnect command is entered
from RPS to terminate the call.
When a Reset Panel is used to terminate the call, a Remote Reset Report is sent to the central
station receiver, and an RPS ACCESS OK is placed into the control panel’s event log. Reports
in the event log that were not sent before the Reset Panel are never sent to the central station
receiver.
When RPS programming changes parameters, a Parameters Changed Report is sent to the
central station receiver. If any programming changes are made, click the Reset Panel check
box and click OK.
When RPS contacts the control panel, the RPS passcode and DataLock code are verified. If
the control panel’s passcode matches and the DataLock code does not, the control panel still
generates a RPS Access OK Event; however, the session ends immediately.
To prevent the control panel from answering the telephone automatically, enter 0 in the
Answer Armed and Answer Disarmed prompts in this section.
3.8.2 Log Threshold Reports
When the event log reaches the percentage configured in Log % Full and the control panel is
properly configured, it will contact Unattended RPS over phone or network.
If communication with RPS is unsuccessful, or if not properly configured, the control panel
generates Log Threshold and Fail to Call RPS events.
Default: Yes (Printer 1 only)
Selection: Yes or No
Default: Yes (Printer 1 only)
Selection: Yes or No
Default: Yes (Printer 1 only)
Selection: Yes or No
Default: Yes (Printer 1 only)
Selection: Yes or No
Default: Yes (Printer 1 only)
Selection: Yes or No
Page view 53
1 2 ... 49 50 51 52 53 54 55 56 57 58 59 ... 209 210

Comments to this Manuals

No comments