Bosch D9412GV4 Installation Guide Page 131

  • Download
  • Add to my manuals
  • Print
  • Page
    / 210
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 130
D9412GV4/D7412GV4/D7212GV4 Points | en 131
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
3 Interior Follower: Interior Follower points are armed only by master arming the area. They are not
armed when using Perimeter-Arming functions.
An Interior Follower point does not create an alarm if it has a fault while the area is in entry delay. An
Interior Follower does not change the amount of remaining entry delay time.
If no entry delay is in effect when a fault occurs for the Interior Follower, it creates an instant alarm.
You must program a delayed Point Response (4, 5, 6, 7, or 8) for an Interior Follower point. The control
panel ignores the entry in P## Entry Delay for an Interior Follower point.
NOTICE!
Increasing the debounce count for Interior Follower points might be necessary to prevent Interior
Follower points from entering into alarm before the control panel recognizes that a Perimeter Delay
point was faulted. Program the Interior Follower’s debounce for one number higher than the debounce
count on Perimeter delay.
4* Keyswitch Maintained: Program P## Point Response as 1. Do not connect initiating devices to a
Keyswitch point.
Normal: The area is disarmed.
Short: A short is a trouble when the area is disarmed. A short is an alarm when the area is armed. When
this point changes from shorted to normal or open, it restores.
Open: When this point changes from normal to open, the area arms.
Program P## Point Response as 2, the point responds as follows:
Normal: When this point changes from open to normal, the area arms.
Open: The area is disarmed.
Short: A short is a trouble when the area is disarmed. A short is an alarm when the area is armed. When
this point changes from shorted to normal or open, it restores.
Trouble and Restoral Reports are not sent if Local While Disarmed is Yes.
Alarm and Restoral Reports are not sent if Local While Armed is Yes.
5* Keyswitch Momentary: Used for area arming and disarming. P## Point Response must be programmed
1. Do not connect initiating devices to a Keyswitch point.
N S N: When this point momentarily changes from normal to shorted to normal, it toggles the armed
state of the area.
Open: An open is a trouble while the point is disarmed. An open is an alarm while the point is armed.
When this point changes from open to normal, it restores.
Trouble and Restoral Reports are not sent if Local Disarmed is Yes.
6* Open/Close Point: Used for point arming and disarming. P## Point Response
must be programmed 1.
Local bells are silenced through the keypad.
Normal: The point is armed and sends a Point Closing Report. A Point Closing Report is not sent if Local
Armed is Yes.
Open: An open is an alarm when the point is armed. An open is a trouble when the point is disarmed.
Alarm and Restoral Reports are not sent if Local Disarmed is Yes.
Short: The point is disarmed and sends a Point Opening Report. A Point Opening Report is not sent if
Local Armed is Yes.
Default Refer to the program record sheet
Page view 130
1 2 ... 126 127 128 129 130 131 132 133 134 135 136 ... 209 210

Comments to this Manuals

No comments