154 en | Schedules (Skeds) D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
6 Schedules (Skeds)
6.1 Windows
Use this programming module to define the windows for Opening and Closing and User
Access.
6.1.1 Opening and Closing
Use these windows to set a schedule for disarming and arming. The disarming and arming
schedules have several independent features:
Suppress normal Opening or Closing Reports when A# Disable O/C in Windows is
programmed as Yes.
Generate a Fail to Open Report if the area is not disarmed on schedule when A# Fail To
Open is programmed as Yes.
Provide a warning tone and a PLEASE CLOSE NOW display at the keypad when it is time
to arm the area.
Generate a Fail to Close Report if the area is not armed on schedule when A# Fail To
Close is programmed as Yes.
Automatically arm the area at the end of the Closing Window when A# Auto Close is
programmed as Yes.
Opening and closing schedules can be set up independently. For example, if you want to use
features provided only by Closing Windows, leave times at default (00:00) in the Opening
Windows prompts and program Closing Window times.
A worksheet is provided at the end of this section for your convenience. Following the
worksheet are examples of programming Opening and Closing Windows for particular
applications (refer to Figure 6.5, Page 161 through Figure 6.9, Page 162).
About the program record sheet: A column labeled Sked # is found in the program record
sheet provided with the control panel. The numbers in that column appear in D6500 and
D6600 reports and local printer reports when the window Begin Time executes.
Window selections 1 through 8 correspond with odd-numbered Skeds 41 through 55 for Open
Window and correspond with even numbered Skeds 42 through 56 for Close Window. For
example, when the Opening Window for Window 1 executes, a Sked 41 Executed event is
generated. Refer to Table 6.1, Page 154.
Table 6.1 Window Selections
Windows
W# Sunday
Selection Sked # Window Sked # Window
141Open42Close
243Open44Close
345Open46Close
447Open48Close
549Open50Close
651Open52Close
753Open54Close
855Open56Close
Default: No
Selection: Yes or No
Yes Activate this window on Sundays.
No Do not activate this window on Sundays.