Bosch D9412GV4 Installation Guide Page 91

  • Download
  • Add to my manuals
  • Print
  • Page
    / 210
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 90
D9412GV4/D7412GV4/D7212GV4 Panel and Area Wide Parameters | en 91
Bosch Security Systems, Inc. Program Entry Guide F.01U.218.312 | 04 | 2012.03
Figure 3.4 Softkey Locations on the D1260 Keypad
Programming Custom Function Keystrokes
Find the command you want to execute in the User Interface section of the program
record sheet. Single digit commands must be programmed with 9 as the second digit.
Table 3.16 CF### Custom Function Keystrokes
When CF### Custom Function is programmed with P, the corresponding custom
function number is passcode protected. The CF### Custom Function prompt is under
User Interface > Cmd Center Functions. The passcode protected custom function can be
added to a keypad’s function list by programming its number in the Function List > M#
Function prompt.
128 to 143 Enable Custom Function 128 through 143 (128 through 131 for D7412GV4/
D7212GV4) (Menu Function only): This function determines if a passcode is needed to
Callout Description
1 Softkey 1 (C1)
2 Softkey 2 (C2)
3 Softkey 3 (C3)
4 Softkey 4 (C4)
5 Softkey 5 (C5)
6 Softkey 6 (C6)
7 Softkey 7 (C7)
8 Softkey 8 (C8)
Command Keystrokes
1 (Master arm area) A19
2 (Perimeter instant arm) A29
3 (Perimeter delay arm) A39
6 (Watch mode) A69
7 (Special alert) A79
8 (Perimeter partial arm) A89
9 (Special alert) A99
0 (Bypass a point) A09
Page view 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 209 210

Comments to this Manuals

No comments