204 en | Keypad Tools Menu (Options Not Available in RPS) D9412GV4/D7412GV4/D7212GV4
F.01U.218.312 | 04 | 2012.03 Program Entry Guide Bosch Security Systems, Inc.
11 Keypad Tools Menu (Options Not Available in RPS)
11.1 Service Bypass Menu
11.1.1 Setting Service Bypass (PT NUM 1-247)
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the SERVICE BYPASS option.
2. Press [ENT] to enter the SERVICE BYPASS option.
If no points are bypassed, NO PTS BYPASSED shows. Skip to Step 6. If points are
bypassed, a list of unbypassed points shows.
3. Press [NEXT] to advance through the points in service bypass.
4. Press [ENT] to select the point that needs to have service bypass removed.
5. Press [NEXT] to toggle the SERVICE BYPASS setting, then [ENT] to save.
6. Press [ENT] at the SERVICE BYPASS prompt. The PT NUM 1-247: prompt shows.
7. Press the point number followed by [ENT]. The PT-### SERVICE BYPASS: NO prompt is
shown.
8. Press [NEXT] to toggle the SERVICE BYPASS setting, then [ENT] to save. The keypad
reads POINT BYPASSED.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the Service Bypass option.
2. Press [ENTER] to enter the Service Bypass option.
If no points are bypassed, No Points Bypassed shows. If points are bypassed, a list of
unbypassed points shows.
3. The number of points in service bypass are below the Point Num 1-247: prompt. Enter
the point number followed by [ENTER].
4. Press [ENTER] to make a selection. The keypad reads Point Bypassed.
11.1.2 Resetting Service Bypass
D1255
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the TOOLS MENU
and navigate to the SERVICE BYPASS option.
2. Press [ENT] to enter the SERVICE BYPASS option.
The SERVICE BYPASS prompt alternates with the number of points in service bypass.
3. Press [NEXT] to advance through the points in service bypass.
4. Press [ENT] to select the point that needs to have service bypass removed.
5. Press [NEXT] to toggle the SERVICE BYPASS setting, then [ENT] to save.
6. Press [ESC] at any time to return to the list of points in service bypass to select another
or press [ESC] again to exit.
When the keypad reads PARAMETER SAVED, your selection has been configured.
D1260
1. Refer to Section 2.5.1 Keypad Programming Menu, page 12 to access the Tools Menu and
navigate to the Service Bypass option.
2. Press [ENTER] to enter the Service Bypass option.